RU | EN Mon-Fri 09:00 - 18:00
Air conditioners are designed to continuously maintain the temperature, humidity and volume and purity of air flow .
ROW unit is a multi-split system, designed for high density CED system
HIGH TECHNOLOGY EQUIPMENT VYBOS
DEVELOPMENT AND MANUFACTURE

UNINTERRUPTED POWER SUPPLY VYBOS В-ИБП-Е | 50~600 kVA

7-inch LCD touch display, user-friendly interface in Russian
DSP digital control technology
Double conversion with pure sine wave and high load carrying capacity
Flexible modular principle and easy scalability with all hot-swappable modular designs
Price: on request.
Call: +7 (495) 105 66 98; E-mail: info@vybos.ru
With expandable power up to 400 kVA / 400 kW in each cabinet, and using full DSP control technology, the В-ИБП-E Series is a generation of three-phase modular UPS. All internal modules (power module, charging module and control module) are modular and hot-swappable, ensuring a compact and reliable system. The design with complete isolation between fragile components and the air channel provides the best combination of reliability, functionality and flexibility. In addition, this system uses improved “N+X” parallel operation and redundancy technology, which avoids system failures due to the failure of one element and further increases reliability.

Advantages of В-ИБП-Е| 50~600 KVA

• Ensuring highly efficient operation at low load factor: 96% at 40% rated load
• High power density power module 50kVA/3U
• A 200 kVA system occupies only 0.5 m2
• Built-in power distribution unit (PDU), easy installation and investment savings
• Input power factor > 0.99, THD < 3%, environmental safety, high efficiency and high level of energy saving
• Wide range of input voltages, self-adjusting frequency 50 Hz / 60 Hz, adaptation to all types of networks
• Soft start (soft start) technology increases compatibility with generators to 1:1.1
• Support two frequency conversion modes: 50Hz input/60Hz output and 60Hz input/50Hz output
• Smart hibernation design ensures efficient UPS operation at low load factors
• Improved parallel expansion technology, support 4 devices in parallel
• Sharing batteries in parallel operation, thereby reducing the user's battery costs
• Flexible configuration of charger parameters and battery configuration, choice of number of batteries 30-46 pcs.
&bul; Intelligent battery management (intelligent charging/discharging control and temperature compensation during continuous charging), increasing battery life
 

• Support battery cold start and automatic power start
• The risk control system for fan failure reduces the load on power modules: up to 30% load on the power module if 2 fans fail; up to 50% load on the power module if 1 fan fails
• Front maintenance, top/bottom cable entry
• Full hardware and software protection, powerful self-diagnosis and event log for checks
• Control unit with SNMP, RS485 and dry contact support
 V-UPS-E | 50~ 600 KVA



Specifications В-ИБП-Е | 50~600 KVA

  В66200 В66300 В66400 В66500 В66600
МОДЕЛЬ
Power   200 kVA 300 kVA 400 kVA 500 kVA 600 kVA
Number of power modules   4 6 8 10 12
Rated power of the power module kVA 50
ENTRANCE
Input wires B 3 phases, neutral and protective ground
Rated voltage   380 / 400 / 415 AC
Voltage range B 138-485 AC (305-485 AC without derating; 138-305 AC with 40% ramp-down)
Input frequency Hz 40-70
Power factor   ≥ 0.99
Current distortion   ≤ 3%
BATTERIES
Sealed maintenance-free lead-acid (AGM or GEL technology with a service life of 5 years; 10 years)
Battery voltage B ± 240 DC (± 180, ± 192, ± 204, ± 216, ± 228, ± 252, ± 264, ± 276 to choose from)
Number of batteries   40 pcs. 12V batteries (support 30 / 32 / 34 / 36 / 38 / 42 / 44 / 46 pcs)
EXIT
Output wires   3 phases, neutral and protective ground
Rated voltage B 380 / 400 / 415 AC
Frequency Hz Synchronizes with the network in mains power mode: 50 / 60 ± 0.25%, in battery mode:
Power factor   0.9
Voltage distortion % ≤ 1 with linear load / ≤ 3 with nonlinear load
Crest factor   3:1
The ability of the inverter to withstand overloads   105% < load ≤ 110%: transfer to bypass after 60 minutes; 110% < load ≤ 125%: transfer to bypass after 10 minutes; 125% < load ≤ 150%: transfer to bypass after 1 min; Load > 150%: transfer to bypass after 200 ms
The ability of the bypass to withstand overloads   Load ≤ 135% for long-term work; < 1000% load for 100 ms
SYSTEM
Efficiency % 96
Max. number of parallel devices   4 devices
Transition time ms 0
Protection   Short circuit protection, overload protection, overheat protection, low battery voltage protection, over/under output voltage protection, fan failure protection, etc.
Communication   RS485, dry contacts, SNMP
Display   7-inch LCD touchscreen
OTHER
Operating temperature °C 0-40
Storage temperature °C - 40 - 70
Humidity % 0 - 95 (no condensation)
Height m ≤ 1000. Above 1000, 1% reduction for each additional 100
Degree of protection   IP 20
Noise level at 1 m DB < 65 < 68
Cabinet dimensions (W x D x H) mm 600 X 850 X 2000 1200 X 850 X 2000 1400 X 850 X 2000
UPS module dimensions (W x T x H) mm 442 X 620 X 130
Cabinet weight kg 213 228 426 448 568
UPS module weight kg 32