Advantages В-ИБП-Д | 1 ~ 3 kVA• Output power factor 0.9
• Double conversion • Operating in ECO mode for energy saving purposes • Selecting the output voltage on the LCD display • Bypass mode output setting on LCD display • Power-on self-test • Improved battery management • Short circuit and overload protection • Automatic charging when switched off • Automatic fan speed control when load changes • Standard RS232 communication port and RJ45 protection • Optional USB/SNMP communication port • Optional Emergency Power Off (EPO) • Optional external battery |
Rear panel 1. Overcurrent protection 2. AC input 3. Modem/phone/ fax 4. DC input 5. Output connectors 6. Fan 7. RS232 8. EPO (optional) 9. USB (optional ) 10. Slot for control cards |
Technical characteristics В-ИБП-Д | 1~3kVA
В901PSRT | В901PHRT | В915PS | В915PSRT | В902PSRT | В902PHRT | В903PSRT | В903PHRT | |||||||
MODEL | ||||||||||||||
Power | |
1 kVA 900 W |
1.5 kVA 1350 kW |
2 kVA 1800 W |
3 kVA 2700 W |
|||||||||
ENTRANCE | ||||||||||||||
Voltage | B | 208 / 220 / 230 / 240 AC | ||||||||||||
Voltage range | B | 110-176 AC (linear reduction between 50% and 100% load); 176-280 AC (without reduction); 280-300 AC (50% reduction) |
||||||||||||
Frequency | Hz | 40-70 | ||||||||||||
Power factor | ≥ 0.99 | |||||||||||||
Bypass voltage range | -25%- + 15% (configurable) | |||||||||||||
EXIT | ||||||||||||||
Voltage | B | 208 / 220 / 230 / 240 AC (adjustable on LCD) | ||||||||||||
Voltage adjustment | ± 1% | |||||||||||||
Frequency | Hz | 45-55 or 55-65 (synchronized range); 50-60 ± 0.1 (battery mode) | ||||||||||||
Waveform | Sinusoidal | |||||||||||||
Crest factor | 3:1 | |||||||||||||
Harmonic distortion | ≤ 2% (linear load); ≤ 5% (non-linear load) | |||||||||||||
Transition time | ms | From mains mode to battery mode: 0 From inverter mode to bypass mode: 0 (standard) |
||||||||||||
Ability to withstand overload | 105%-125%: switch to bypass after 1 minute; 125%-150%: transfer to bypass after 30 s; > 150%: transfer to bypass after 300 ms |
|||||||||||||
EFFICIENT | ||||||||||||||
Mains mode | ≥ 92% | |||||||||||||
ECO mode | ≥ 95% | ≥ 96% | ≥ 97% | |||||||||||
BATTERIES | ||||||||||||||
Sealed maintenance-free lead-acid (AGM or GEL technology with a service life of 5 years; 10 years) | ||||||||||||||
DC voltage | B | 24 | 36 | 36 | 48 | 72 | 48 | 72 | 48 | 72 | 72 | 72 | 96 | 96 |
Built-in battery | Ah | 2 X 9 | 3 X 7 | / | 4 X 9 | 6 X 7 | 4 X 9 | 6 X 7 | 4 X 9 | 6 X 7 | / | 6 X 9 | 8 X 7 | / |
Charging current (max.) | A | 1 | 6 | 1 | 6 | 1 | 6 | |||||||
Charging time | h | 3 | ||||||||||||
Battery life | min | 5 | ||||||||||||
ALARMS | ||||||||||||||
Power failure | 4 s signal | |||||||||||||
Bottom. battery charge level | 1 s signal | |||||||||||||
Overload | two beeps lasting 1 second | |||||||||||||
UPS failure | long signal | |||||||||||||
COMMUNICATION | ||||||||||||||
RS232 (standard) / USB (optional) | Windows support® 98 / 2000 / 2003 / XP / Vista / 2008 / Windows® 7 / 8 / 10 | |||||||||||||
SNMP (optional) | Power management using SNMP manager and web browser | |||||||||||||
OTHER | ||||||||||||||
Operating temperature | °C | 0-40 | ||||||||||||
Relative humidity | % | 0-90 (no condensation) | ||||||||||||
Noise level | DB | ≤ 50 (1 m ) | ||||||||||||
Rack mountable | DB | yes | no | yes | ||||||||||
Dimensions (W x D x H) | mm | 440 X 468 X 88 | 440 X 658Х88 | 440Х468Х88 | 440Х658Х88 | 440X468X88 (UPS) 440X440XX86 (BAT) | 440X468X88 | |||||||
Dimensions in packaging (W x D x H) | mm | 545 X 592 X 198 | 545Х782Х198 | 545Х592Х198 | 545Х782Х198 | 545Х592Х198 590Х580Х200 (BAT) |
545X592X198 | |||||||
Net weight (kg) | kg | 12.26 | 13.78 | 7.58 | 22.73 | 25.86 | 22.73 | 25.86 | 22.73 | 25.86 | 9.66 | 29.26 | 9.45 (UPS) 27.2 (BAT) |
10.04 |
Gross weight (kg) | 15.78 | 17.3 | 11.1 | 26.63 | 29.76 | 26.63 | 29.76 | 26.63 | 29.76 | 13,18 | 33.16 | 12.97 (UPS) 30.2 (BAT) |