Advantages В-ИБП-А1 | 10 ~ 30 kVA
|
1. AC input 2. DC input 3. Bypass input 4. Output 5. Circuit breaker mains input 6. Bypass input circuit breaker 7. Maintenance bypass 8. Fan 9. RS232 10. USB 11. EPO (emergency power off) 12. Battery temperature compensation (optional) 13. Smart control card slot 1 (SNMP / AS400 / RS485 options) 14. Smart control card slot 2 ( SNMP / AS400 / RS485 options) 15. Parallel board (optional) 16. Battery kill switch |
Specifications В-ИБП-А1 | 10~ 30 КВА
В9010P | В9015P | В9020P | В9030P | ||
MODEL | |||||
Power | 10 kVA 9 kW |
15 kVA 13.5 kW |
20 kVA 18 kW |
30 kVA 27 kW |
|
ENTRANCE | |||||
Rated voltage | B | 360 / 380 / 400 / 415 AC | |||
Voltage range | B | 277-485 AC (without reduction); 190-277 AC (linear reduction between 50% and 100% load) |
|||
Rated frequency | Hz | 50 / 60 (self-tuning) | |||
Frequency range | Hz | 40-70 | |||
Power factor | ≥ 0.99 | ||||
Total Harmonic Distortion (THDI) | ≤ 5% | ||||
Bypass voltage range | -40% - + 15% (configurable) | ||||
EXIT | |||||
Voltage | B | 360 / 380 / 400 / 415 AC (configurable) | |||
Voltage adjustment | ± 1% | ||||
Frequency | Hz | 45-55 or 55-65 (synchronized range); 50-60 ± 0.1 (battery mode) |
|||
Waveform | Sinusoidal | ||||
Crest factor | 3:1 | ||||
Harmonic distortion | ≤ 2% (linear load); ≤ 5% (non-linear load) | ||||
Transition time | ms | From mains mode to battery mode: 0 From inverter mode to bypass mode: 0 (standard) |
|||
The ability of the inverter to withstand overloads | 102%-125%: switch to bypass after 10 minutes; 125%-150%: transfer to bypass after 1 minute; > 150%: transfer to bypass after 0.5 s |
||||
The ability of the bypass to withstand overloads | 102%-125%: shutdown after 20 minutes; 125%-150%: shutdown after 2 minutes; > 150%: shutdown after 1 s |
||||
BATTERIES | |||||
Sealed maintenance-free lead-acid (AGM or GEL technology with a service life of 5 years; 10 years) | |||||
DC voltage | B | Standard model: 240 DC; Long-term model: 192 DC (168 / 192 / 216 / 240 options) |
|||
Built-in battery in standard model | Ah | 20 X 7 | 40 X 7 | 40 x 9 | 60 x 9 |
Recharge time | h | Standard model (S): 90% of capacity is restored in 4 hours; Long runtime model (H): dependent on battery capacity |
|||
SYSTEM | |||||
Efficiency | % | ≥ 93, ECO mode 98 | |||
Display | LCD display + SD display (LED display) | ||||
Alarms | Battery mode, low battery voltage, fan failure, etc. | ||||
Max. number of parallel connected devices | 6 | ||||
COMMUNICATION | |||||
RS232 (standard) / USB (optional) | Windows support® 98 / 2000 / 2003 / XP / Vista / 2008 / Windows® 7 / 8 / 10 | ||||
SNMP (optional) | Power management using SNMP manager and web browser | ||||
OTHER | |||||
Humidity | % | 20-90 relative humidity at a temperature of 0-40° C (no condensation) | |||
Noise level | DB | ≤ 60 (1 m) | ≤ 65 (1 m) | ||
Dimensions (W x D x H) | mm | 350 X 655 X 732 (H) | |||
mm | 350 X 785 X 858 (S) | 350 X 785 X 1078 (S) | |||
Dimensions in packaging (W x D x H) | mm | 472 X 780 X 920 (H) | |||
mm | 472 X 910 X 1050 (S) | 472 X 910 X 1260 (S) | |||
Net weight | kg | 55 (H), 115 (S) | 60 (H), 155 (S) | 61 (H), 175 (S) | 65 (H), 235 (S) |