BLOCK IDENTIFICATION
1 | 2 | 3 | 4,5,6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 |
В | Р | 6 | 050 | В | Т | Э | 1 | С | И | Н | 00 |
1. MANUFACTURER B - VYBOS 2. SERIES Р - inter-row 3. SIZE: WIDTH 3=300 mm 5=500 mm 6=600 mm 4,5,6. NOMINAL COOLING CAPACITY: Nominal cooling capacity, kW |
7. TYPE: Ф = Precision air conditioners with a remote air-cooled condenser B = Precision air conditioners with a built-in water-cooled condenser X = Precision air conditioners using cold (chiller) water 8. AIR DIRECTION (DISCHARGE) T = rear suction, forward discharge Д = closed circuit, side suction/discharge Л = closed circuit, left suction/discharge П = closed kennel, suction/discharge on the right |
9. TYPE OF FAN Э = Electronically commutated A = Asynchronous 10. TYPE OF REFRIGERANT 0 = water 1 = R410A 2 = R407C 3 = R134A 11. MODIFICATION C = Standard (compressor located inside) K = Compressor located outside< /td>12. COMPRESSOR TYPE 0 = without compressor 1 = compressor with “on off” И = compressor with inverter (frequency) control 13. COOLANT SUPPLY SIDE B = top H = bottom 14. CONSTRUCTION: 00 = Standard XX = Non-standard |
ВР3 В SERIES Model range: ВР3015В | ВР3020В | ВР3025В
|
ВР3 В - a market-leading data center and electronics cooling solution, an innovative and efficient thermal management system for rooms, rows and racks, from small computer rooms to large mission-critical data centers .
Full control of the cooling of your room |
Possibility of developing a constructive solution for a specific project |
Compatible with communication protocols (Modbus, SNMP, Lonworks, Bacnet, etc.), BMS building management systems and engineering systems | Equipped with a wide range of additional options |
BP3 В BASIC OPTIONS
Basic options for in-row air conditioners of the BP3 Ф series. List of basic equipment used with cPCO controllers.
See table for ВР3 В
See table for ВР3 В
DETAILED TECHNICAL CHARACTERISTICS OF ВР3 В SERIES
ВР 3 015 В | BP 3 020 В | BP 3 025 В | ||
Indoor unit model | ВК 019 СТД Н | ВК 028 СТД Н | ВК 033 СТД Н | |
Number of external blocks | 1 | 1 | 1 | |
EQUIPMENT PARAMETERS | ||||
Power supply | 380/3ph/50Hz+N+PE | |||
Total cooling capacity | kW | 16,18 | 20.56 | 25.6 |
Sensible cooling capacity | kW | 15.50 | 20.38 | 24.7 |
SHR | 0.96 | 0.99 | 0.96 | |
FAN SECTION | ||||
Air flow | m3/h | 2200 | 3200 | 4000 |
Maximum power consumption | kW | 0.16 | 0.16 | 0.16 |
Maximum operating current | A | 1.26 | 1.26 | 1.26 |
Maximum external static pressure | Pa | 250 | 250 | 250 |
Number of fans | pcs | 4 | 5 | 5 |
COMPRESSOR | ||||
Number of compressors / circuits | 1 | 1 | 1 | |
Compressor type | Spiral | Spiral | Spiral | |
Rated power consumption | kW | 4.33 | 5.18 | 6.5 |
Rated operating current | A | 9.5 | ||
Maximum operating current | A | 8,8 | 10.89 | 15.5 |
HUMIDIFICATION | ||||
Steam capacity | kg/h | 3 | 3 | 3 |
Rated power consumption | kW | 2,2 | 2,2 | 2,2 |
Maximum operating current | A | 10.2 | 10.2 | 10.2 |
ELECTRIC HEATER | ||||
Number of steps | 1 | 1 | 1 | |
Rated power consumption/heating power | kW | 4.26 | 4.26 | 4.26 |
Maximum operating current | A | 6,7 | 6,7 | 6,7 |
AIR FILTERS | ||||
Filter class | G4 | G4 | G4 | |
EVAPORATOR | ||||
Evaporator volume | dm3 | 6.13 | 6.13 | 6.13 |
SOUND PRESSURE | ||||
Sound pressure level ³ | dB | 63 | 71 | 76 |
OVERALL DIMENSIONS | ||||
Width | mm | 300 | 300 | 300 |
Depth | mm | 1000|1200 | 1000|1200 | 1000|1200 |
Height | mm | 1998 | 1998 | 1998 |
Weight ² | kg | 190 | 185 | 190 |
CONNECTING DIMENSIONS | ||||
Gas pipe diameter | mm | 16 | 16 | 16 |
Diameter of liquid pipe | mm | 12 | 12 | 16 |
Water supply diameter for humidifier | Inch | ¾ | ¾ | 3/4 |
Diameter of water drainage from the humidifier | mm | 32 | 32 | 32 |
Condensate drain diameter | mm | 20 | 20 | 20 |
ВР6 В SERIES Model range: ВР6035В | ВР6050В
|
ВР6 В - a line of in-row air conditioners, provides an effective, flexible, economical and reliable approach to creating comfortable conditions in data centers, telecommunications centers and server rooms. Take complete control of your data center cooling.
Full control of the cooling of your room |
Possibility of developing a constructive solution for a specific project |
Compatible with communication protocols (Modbus, SNMP, Lonworks, Bacnet, etc.), BMS building management systems and engineering systems | Equipped with a wide range of additional options |
BP6 В BASIC OPTIONS
Basic options for in-row air conditioners of the ВР6 Ф series. List of basic equipment used with cPCO controllers.
See table for ВР6 В
See table for ВР6 В
DETAILED TECHNICAL CHARACTERISTICS OF ВР6 В SERIES
BP 6 035 В | BP 6 050 В | |||||
Indoor unit model | ВК 050 СТД Н | ВК 064 СТД Н | ||||
Number of external blocks | 1 | 1 | ||||
EQUIPMENT PARAMETERS | ||||||
Power supply | 380/3ph/50Hz+N+PE | |||||
Total cooling capacity | kW | 37.3 | 51.6 | |||
Sensible cooling capacity | kW | 37.3 | 48.4 | |||
SHR | 1 | 0.94 | ||||
FAN SECTION | ||||||
Air flow | m3/h | 6000 | 6850 | |||
Maximum power consumption | kW | 1,1 | 1,1 | |||
Maximum operating current | A | 1.76 | 1.76 | |||
Maximum external static pressure | Pa | 381 | 250 | |||
Number of fans | pcs | 2 | 2 | |||
COMPRESSOR | ||||||
Number of compressors / circuits | 1 | 1 | ||||
Compressor type | Spiral | Spiral | ||||
Rated power consumption | kW | 11.6 | 13.06 | |||
Rated operating current | A | |||||
Maximum operating current | A | 19.8 | 26.64 | |||
HUMIDIFICATION | ||||||
Steam capacity | kg/h | 3 | 3 | |||
Rated power consumption | kW | 1.07 | 1.07 | |||
Maximum operating current | A | 8.2 | 8.2 | |||
ELECTRIC HEATER | ||||||
Number of steps | 1 | 1 | ||||
Rated power consumption/heating power | kW | 4.32 | 4.32 | |||
Maximum operating current | A | 6,7 | 6,7 | |||
AIR FILTERS | ||||||
Filter class | G4 | G4 | ||||
EVAPORATOR | ||||||
Evaporator volume | dm3 | 8.2 | 11.07 | |||
SOUND PRESSURE | ||||||
Sound pressure level ³ | 76 | 87 | 87 | |||
OVERALL DIMENSIONS | ||||||
Width | mm | 600 | 600 | |||
Depth | mm | 1000|1200 | 1200 | |||
Height | mm | 1998 | 1998 | |||
Weight ² | kg | 280 | 335 | |||
CONNECTING DIMENSIONS | ||||||
Gas pipe diameter | mm | 18 | 28 | |||
Diameter of liquid pipe | mm | 16 | 22 | |||
Water supply diameter for humidifier | Inch | 3/4 | ¾ | |||
Diameter of water drainage from the humidifier | mm | 32 | 32 | |||
Condensate drain diameter | mm | 20 | 20 |
¹ – dry bulb
² – weight of basic equipment
³ – sound pressure level for free space conditions at a distance of 1 meter