RU | EN Mon-Fri 09:00 - 18:00
Air conditioners are designed to continuously maintain the temperature, humidity and volume and purity of air flow .
ROW unit is a multi-split system, designed for high density CED system
HIGH TECHNOLOGY EQUIPMENT VYBOS
DEVELOPMENT AND MANUFACTURE

CABINET PRECISION AIR CONDITIONERS WITH REMOTE AIR CONDENSER

The heat from the technical room is dissipated by an external finned coil condenser, connected during installation. Remote condensers are available in standard and silenced version.

BLOCK IDENTIFICATION

1 2 3 4,5,6 7 8 9 10 11 12 13 14

В Ш Б 058 Ф Н Э 1 С И 0 X

 

1. MANUFACTURER
В - VYBOS

2. SERIES
Ш - cabinet

3. COOLING CAPACITY RANGE:
М = SMALL
C = MEDIUM
Б = LARGE
Э = EXTRA

4,5,6. NOMINAL
COOLING CAPACITY:
Nominal
cooling capacity,
kW
7. TYPE:
Ф = Precision air conditioners with a remote air-cooled condenser
B = Precision air conditioners with a built-in water-cooled condenser
X = Precision air conditioners using cold (chiller) water

8. DIRECTION AIR (DISCHARGE):
H = Suction vertically from above, discharge vertically downwards
B = Suction vertically from below, delivery vertically upwards
B = Suction from below, delivery vertically upwards
F = Suction top, front feed bottom front
9. TYPE OF FAN
Э = Electronically commutated
A = Asynchronous

10. TYPE OF REFRIGERANT
0 = water
1 = R410A
2 = R407C
3 = R134A

11. MODIFICATION
C = Standard (compressor located inside)
K = Compressor located outside< /td>12. COMPRESSOR TYPE
0 = without compressor
1 = compressor with “on-off”
И = compressor with inverter (frequency) control

13. COOLANT SUPPLY SIDE
0 = choice not available

14. CONSTRUCTION:
0 = Standard
X = Custom

 

 

Шкафные кондиционеры ВШМ

ВШМ Ф SERIES
Model range: ВШМ007Ф | ВШМ009Ф | ВШМ011ФН | ВШМ014ФБ | ВШМ014ФН | ВШМ016ФБ | ВШМ016ФБ(inv) | ВШМ016ФН | ВШМ019ФБ | ВШМ019ФН | ВШМ021ФБ | ВШМ021ФН(inv) | ВШМ021ФН

  • Refrigerant: Freon
  • Total cooling capacity:8-23.7 kW
  • Power supply: 230V/1ph+PE, 380/3ph+N+PE
  • Air flow: 2050-5400 m3/h
  • Dimensions (WxDxH):(600-770) x (500-750) x (1750.1980) mm
  • Weight:140-260 kg

Find out price

 

ВШМ Ф - a line of compact cabinet air conditioners with a cabinet width of 600, 670 or 770 mm. Compact cabinet air conditioners are equipped with energy-efficient components and are characterized by flexible cooling of rooms and buildings with a high heat density.
The small footprint, lightweight design and ease of installation make the ВШМ Ф ideal for modernization and use in confined spaces.

 

Full control of the cooling
of your room
Possibility of developing
a constructive solution
for a specific project
Compatible with communication protocols (Modbus, SNMP, Lonworks, Bacnet, etc.), BMS building management systems and engineering systems Equipped with a wide range of
additional options

 

BASIC OPTIONS ВШМ Ф

Basic options for cabinet air conditioners of the ВШМ Ф series. List of basic equipment used with cPCO controllers.
See table for ВШМ Ф

 

TECHNICAL DATA ВШМ Ф

    ВШМ
007 Ф
ВШМ 009 Ф ВШМ 011 ФН ВШМ 014 ФБ ВШМ 014 ФН ВШМ 016 ФБ ВШМ 016 ФБ
(inv)
ВШМ 016 ФН ВШМ 019 ФБ ВШМ 019 ФН ВШМ 021 ФБ ВШМ 021 ФН
(inv)
ВШМ 021 ФН
External unit model   ВК 012 ВК 012 ВК 015 ВК 019 ВК 019 ВК 024   ВК 024 ВК 024 ВК 024 ВК 028   ВК 028
Number of external blocks   1 1 1 1 1 1   1 1 1 1   1
INITIAL PARAMETERS
Refrigerant   R410A R410A R410A R410A R410A R410A R410A R410A R410A R410A R410A R410A R410A
Air temperature at the air conditioner inlet ¹ °С 24 24 24 24 24 24 24 24 24 24 24 24 24
Relative air humidity at the air conditioner inlet % 50 50 50 50 50 50 50 50 50 50 50 50 50
Ambient temperature °С 35 35 35 35 35 35 35 35 35 35 35 45 35
Altitude m 0 0 0 0 0 0 0 0 0 0 0 0 0
EQUIPMENT PARAMETERS
Power supply (50 Hz)   230V/1ph+PE 380/3ф+N+PE
Total cooling capacity kW 8 10.3 12.4 16.1 16.1 19.1 17.1 19.1 21.9 21.9 23.7 24.6 23.7
Sensible cooling capacity kW 6.8 8,9 10.6 13.9 13.9 16.1 15.1 16.1 18.7 18.7 20.4 19.9 20.4
SHR   0.85 0.86 0.85 0.86 0.86 0.84 0.88 0.84 0.85 0.85 0.86 0.81 0.86
Outgoing air temperature ° C 14.4 14.3 14.3 13.6 13.6 13.9 14.3 13.9 13.2 13.2 13.1 13.4 13.1
Outgoing air humidity % 84.2 86 84 88 88 86.5 86.2 86.5 90 90 88 84.1 88
FAN SECTION
Air flow m3 /h 2050 2600 3200 3800 3800 4600 4500 4600 5000 5000 5400 5400 5400
Maximum power consumption kW 0.4 0.5 0.69 0.84 0.84 1,4 1,4 1,4 1,2 1,2 1.53 1.53 1.53
Maximum operating current A 2.07 2.7 3.21 3.93 3.93 3.55 3.55 3.55 3.28 3.28 3.87 3.87 3.87
Maximum external static pressure Pa 200 200 400 250 250 600 600 600 600 600 580 580 580
Number of fans pcs 1 1 1 1 1 1 1 1 1 1 1 1 1
COMPRESSOR
Number of compressors / circuits   1 1 1 1 1 1 1/1 1 1 1 1 1/1 1
Compressor type   I/0 I/0 I/0 I/0 I/0 I/0 Inv. I/0 I/0 I/0 I/0 Inv. I/0
Rated power consumption kW 2,1 2,4 3 3.6 3.6 4,3 4,3 4,3 4.75 4.75 5.2 6.5 5.2
Maximum operating current A 22.3 10 13.5 15 15 19 10.3 19 18 18 19 15.5 19
Current with locked rotor A 97 45 60 70 70 87  100 87 100 100 100  125 100
WATER COOLED CONDENSER
Water consumption m3/h 1.96 2.49 3,1 3.92 3.92 4.6   4.6 5.25 5.25 5.68   5.68
Ethylene glycol content % 45 45 45 45 45 45   45 45 45 45   45
Temperature graph °С 35/40 35/40 35/40 35/40 35/40 35/40   35/40 35/40 35/40 35/40   35/40
Condensation temperature °С 45 45 45 45 45 45   45 45 45 45   45
Pressure drop kPa 29.7 41 35.7 28.1 28.1 37.6   37.6 29.8 29.8 34.4   34.4
HUMIDIFICATION
Steam capacity kg/h 3 3 3 5-8 5-8 5-8 5-8 5-8 5-8 5-8 5-8 5-8 5-8
Rated power consumption kW 1.07 1.07 1.07 3.64- 6.06 3.64- 6.06 3.64- 6.06 3.64- 6.06 3.64- 6.06 3.64- 6.06 3.64- 6.06 3.64- 6.06 3.64- 6.06 3.64- 6.06
Maximum operating current A 8.2 8.2 8.2 8.2 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4
ELECTRIC HEATER
Number of steps   1 1 1 1 1 1 1 1 1 1 1 1 1
Rated power consumption/heating power kW 1.42 1.42 1.42 4.32 4.32 4.32 4.32 4.32 4.32 4.32 4.32 4.32 4.32
Maximum operating current A 6.59 6.59 6,7 6,7 6,7 6,7 6,7 6,7 6,7 6,7 6,7 6,7 6,7
AIR FILTERS
Filter class   G4 G4 G4 G4 G4 G4 G4 G4 G4 G4 G4 G4 G4
EVAPORATOR
Evaporator volume dm3 2.62 4.42 4.42 6.17 6.17 6.17 6.17 6.17 7.91 7.91 7.91 7.91 7.91
SOUND PRESSURE
Sound pressure level ³ dB 64 66 67 67 67 76 75 76 76 76 76 70 76
OVERALL DIMENSIONS
Width mm 600 670 670 770 770 770 770 770 770 770 770 770 770
Depth mm 500 500 500 650 650 650 650 650 750 750 750 750 750
Height mm 1750 1750 1750 1980 1980 1980 1980 1980 1980 1980 1980 1980 1980
Weight ² kg 140 170 175 225 225 240 240 240 240 240 250 270 250
CONNECTING DIMENSIONS
Gas pipe diameter* mm 10 12 12 12 12 16 16 16 16 16 16 16 16
Diameter of liquid pipe* mm 10 12 12 16 16 12 12 12 12 16 16 16 16
Water supply diameter for humidifier inch ¾ ¾ ¾ ¾ ¾ ¾ ¾ ¾ ¾ ¾ ¾ ¾ ¾
Diameter of water drainage from the humidifier mm 32 32 32 32 32 32 32 32 32 32 32 32 32
Condensate drain diameter mm 20 20 20 20 20 20 20 20 20 20 20 20 20

 

 

VShS cabinet air conditioners

ВШС Ф SERIES
Model range: ВШС026Ф | ВШС026Ф (inv) | ВШС032ФН | ВШС040Ф | ВШС040Ф(inv) | ВШС050Ф | ВШС050Ф (inv)

  • Refrigerant: Freon
  • Total cooling capacity:29-51.22 kW
  • Power supply: 380/3f+N+PE
  • Air flow: 6100-11300 m3/h
  • Dimensions (width x depth x height): (1100, 1300) x 890 x 1980 mm
  • Weight:380-470 kg

Find out price

 

ВШС Ф - a line of cabinet air conditioners designed specifically for critical applications, provides precise control of temperature and humidity, and air filtration. Improved software management functions with network connection interfaces and flexible system management — both local and remote.
There is a wide range of options and accessories to choose from, which makes it possible to adapt the ВШС Ф system to create the required air conditioning solution.

 

Full control of the cooling
of your room
Possibility of developing
a constructive solution
for a specific project
Compatible with communication protocols (Modbus, SNMP, Lonworks, Bacnet, etc.), BMS building management systems and engineering systems Equipped with a wide range of
additional options

 

BASIC OPTIONS ВШС Ф

Basic options for cabinet air conditioners of the ВШС Ф series. List of basic equipment used with cPCO controllers.
See table for ВШС Ф

 

TECHNICAL DATA ВШС Ф

    ВШС 026 Ф ВШС 026 Ф (inv) ВШС 032 ФН ВШC 040 Ф ВШC 040 Ф (inv) ВШC 050 Ф ВШC 050 Ф (inv)
Модель внешнего блока   ВК 033   ВК 042 ВК 058   ВК 064  
Number of external blocks   1   1 1   1  
INITIAL PARAMETERS
Refrigerant   R410A R410A R410A R410A R410A R410A R410A
Air temperature at the air conditioner inlet ¹ °С 24 24 24 24 24 24 24
Relative air humidity at the air conditioner inlet % 50 50 50 50 50 50 50
Ambient temperature °С 35 35 35 35 35 35 35
Altitude m 0 0 0 0 0 0 0
EQUIPMENT PARAMETERS
Power supply (50 Hz)   380/3ф+N+PE
Total cooling capacity kW 29 28 36.4 43.8 43.72 51.22 52.76
Sensible cooling capacity kW 24.7 23.94 31.6 35.3 34.84 44.5 43.39
SHR   0.85  0.85 0.87 0.81  0.79 0.86  0.84
Outgoing air temperature °С 12.3  12.6 13.2 11.8  11.8 12.6  12.9
Outgoing air humidity % 91  93.5 87 93  93 90.1  90
FAN SECTION
Air flow m3/h 6100  6100 8500 8300  8300 11300  11300
Maximum power consumption kW 1.75  1.75 2.9 2.6  2.6 1.6  1.6
Maximum operating current A 4.43  4.43 6.32 5.84  5.84 4.2  4,2
Maximum external static pressure Pa 550  550 260 300  300 600  600
Number of fans pcs 1  1 1 1  1 2  2
COMPRESSOR
Number of compressors / circuits   1  1/1 1 1  1/1 1  1/1
Compressor type   I/0  Invert. I/0 I/0  Invert. I/0  Invert.
Rated power consumption kW 6.5  6.5 8.6 9.8  10.5 11.5  12.85
Maximum operating current A 26  13.63 30 35  35 38.6  20.17
Current with locked rotor A 125  128 147 158  158 197  
КОНДЕНСАТОР С ВОДЯНЫМ ОХЛАЖДЕНИЕМ
Расход воды м3/ч 7,05   8,83 10,6   5,68  
Содержание этиленгликоля % 45   45 45   45  
Температурный график °С 35/40   35/40 35/40   35/40  
Температура конденсации °С 45   45 45   45  
Перепад давления кПа 33,6   39,7 38   49,3  
УВЛАЖНЕНИЕ
Паропроизводительность кг/ч 5-8  5-8 5-8 5-8  5-8 5-8  5-8
Номинальная потребляемая мощность кВт 3,64- 6,06  3,64-6,06 3,64- 6,06 3,64- 6,06  3,64-6,06 3,64- 6,06  3,64-6,06
Максимальный рабочий ток А 9,4  9,4 9,4 9,4  9,4 9,4  9,4
ЭЛЕКТРИЧЕСКИЙ НАГРЕВАТЕЛЬ
Количество ступеней   1  4 1 2  2 2  2
Номинальная потребляемая мощность/мощность нагрева кВт 4,32  4,32 4,32 8,64  8,64 8,64  8,64
Максимальный рабочий ток А 6,7  6,7 6,7 13,4  13,4 13,4  13,4
ВОЗДУШНЫЕ ФИЛЬТРЫ
Класс фильтра   G4  G4 G4 G4  G4 G4  G4
ИСПАРИТЕЛЬ
Объем испарителя дм3 13,28  13,28 13,28 17,58  17,58 17,58  17,58
ЗВУКОВОЕ ДАВЛЕНИЕ
Уровень звукового давления ³ дБ 76  70 76 76  74 76  80
ГАБАРИТНЫЕ РАЗМЕРЫ
Ширина мм 1050  1050 1050 1300  1300 1300  1300
Глубина мм 890  890 890 890  890 890  890
Высота мм 1980  1980 1980 1980  1980 1980  1980
Вес ² кг 370  370 378 470  390 475  640
ПОДСОЕДИНИТЕЛЬНЫЕ РАЗМЕРЫ
Диаметр газовой трубы* мм 18  18 18 22  22 22  22
Диаметр жидкостной трубы* мм 16  16 16 18  18 18  18
Диаметр подачи воды для увлажнителя дюйм ¾  ¾ ¾ ¾  ¾ ¾  ¾
Диаметр дренажа воды от увлажнителя мм 32  32 32 32  32 32  32
Диаметр дренажа конденсата мм 20  20 20 20  20 20  20

 

 

Шкафные кондиционеры ВШБ

ВШБ Ф SERIES
Model range: ВШБ058ФН | ВШБ065ФН | ВШБ075Ф | ВШБ100Ф | ВШБ110Ф

  • Refrigerant: Freon
  • Total cooling capacity:63.4-130 kW
  • Power supply: 380/3f+N+PE
  • Air consumption: 14700-24000 m3/h
  • Dimensions (width x depth x height): (2060, 2580) x 890 x 1980 mm
  • Weight:630-1015 kg

Find out price

 

ВШБ Ф - The line of cabinet air conditioners is based on today's advanced cooling technologies, providing precise temperature control, optimal airflow distribution and high cooling capacity in data centers and other critical applications.
There is also a wide range of options and accessories to choose from, which makes it possible to adapt the ВШБ Ф system to create the necessary air conditioning solution.

 

Full control of the cooling
of your room
Possibility of developing
a constructive solution
for a specific project
Compatible with communication protocols (Modbus, SNMP, Lonworks, Bacnet, etc.), BMS building management systems and engineering systems Equipped with a wide range of
additional options

 

BASIC OPTIONS ВШБ Ф

Basic options for cabinet air conditioners of the ВШБ Ф series. List of basic equipment used with cPCO controllers.
See table for ВШБ Ф

 

TECHNICAL DATA ВШБ Ф

    ВШБ 058 ФН ВШБ 065 ФН ВШБ 075 Ф ВШБ 100 Ф ВШБ 110 Ф
Модель внешнего блока   ВК 042 ВК 050 ВК 058 ВК 064 ВК 072
Number of external blocks   2 2 2 2 2
INITIAL PARAMETERS
Refrigerant   R410A R410A R410A R410A R410A
Air temperature at the air conditioner inlet ¹ °С 24 24 24 24 24
Relative air humidity at the air conditioner inlet % 50 50 50 50 50
Ambient temperature °С 35 35 35 35 35
Altitude m 0 0 0 0 0
EQUIPMENT PARAMETERS
Power supply (50 Hz)   380/3ф+N+PE
Total cooling capacity kW 63.4 79.5 90 102.44 130
Sensible cooling capacity kW 57.2 66.6 72 87.24 100
SHR   0.9 0.84 0.8 0.83 0.78
Outgoing air temperature °С 12.7 12 11.9 12.5 11.9
Outgoing air humidity % 91.5 92 92 90.4 90.1
FAN SECTION
Air flow m3/h 14700 16100 17300 22000 24000
Maximum power consumption kW 2,1 2,4 3,1 1.5 2,4
Maximum operating current A 5.1 5,6 6.5 4.2 5,6
Maximum external static pressure Pa 400 350 300 500 400
Number of fans pcs 2 2 2 3 3
COMPRESSOR
Number of compressors / circuits   2/ 2 2/ 2 2/ 2 2/ 2 2/ 2
Compressor type   I/0 I/0 I/0 I/0 I/0
Rated power consumption kW 13 17.4 20 23.1 30.3
Maximum operating current A 52 60 70 77.2 102
Current with locked rotor A 125 147 158 197 215
WATER COOLED CONDENSER
Water consumption m3/h 7.64 9.4 10.77 12.34 15.68
Ethylene glycol content % 45 45 45 45 45
Temperature graph °С 35/40 35/40 35/40 35/40 35/40
Condensation temperature °С 45 45 45 45 45
Pressure drop kPa 39.1 44.8 39.3 50.8 39.6
HUMIDIFICATION
Steam capacity kg/h 5-8 5-8 5-8 5-8 5-8
Rated power consumption kW 3.64- 6.06 3.64- 6.06 3.64- 6.06 3.64- 6.06 3.64- 6.06
Maximum operating current A 9.4 9.4 9.4 9.4 9.4
ELECTRIC HEATER
Number of steps   2 2 2 3 3
Rated power consumption/heating power kW 8.64 8.64 8.64 12.96 12.96
Maximum operating current A 13.4 13.4 13.4 20.1 20.1
AIR FILTERS
Filter class   G4 G4 G4 G4 G4
EVAPORATOR
Evaporator volume dm3 26.56 26.56 35.16 35.16 35.16
SOUND PRESSURE
Sound pressure level ³ dB 76 76 76 79 79
OVERALL DIMENSIONS
Width mm 2060 2060 2550 2550 2550
Depth mm 890 890 890 890 890
Height mm 1980 1980 1980 1980 1980
Weight ² kg 630 660 730 785 1015
CONNECTING DIMENSIONS
Gas pipe diameter* mm 2x18 2x18 2x28 2x28 2x28
Diameter of liquid pipe* mm 2х16 2х16 2x22 2x22 2x22
Water supply diameter for humidifier inch ¾ ¾ ¾ ¾ ¾
Diameter of water drainage from the humidifier mm 32 32 32 32 32
Condensate drain diameter mm 20 20 20 20 20

¹- dry bulb
¹ - weight of basic equipment
³ - sound pressure level for free space conditions at a distance of 1 meter
* - is not the diameter of the pipeline between the indoor and outdoor units. See "Installation and Operating Instructions"