Main components |
Execution |
||
Grilles with adjustable flow direction Silencers Electronically commutated fan Heat exchanger Load base Screws for quick removal of panels |
![]() |
![]() |
Technical characteristics ВСУ008ХБ
Indoor unit model | ВСУ008ХБ | |
External block model | - | |
Number of external blocks | - | |
INITIAL PARAMETERS | ||
Coolant type | Water | |
Coolant inlet temperature | °С | 7 |
Outlet coolant temperature | °С | 12 |
Air temperature at the air conditioner inlet | °С | 24 |
Relative humidity at the air conditioner inlet | % | 50 |
Ambient temperature | °С | - |
Altitude | m | - |
EQUIPMENT PARAMETERS | ||
Power supply | 220V/1ph/50Hz+N+PE | |
Total cooling capacity | kW | 10 |
Sensible cooling capacity | kW | 8.5 |
SHR | 0.85 | |
Air temperature at the outlet of the air conditioner | °С | 11.4 |
Air humidity at the outlet of the air conditioner | % | 90 |
FAN SECTION | ||
Air flow | m3/h | 1800 |
Rated power consumption | kW | 0.27 |
Maximum operating current | A | 2,1 |
Maximum external static pressure | ||
Number of fans | pcs | 1 |
AIR FILTERS | ||
Filter class | G4 | |
SOUND PRESSURE | ||
Sound pressure level | dB | 35 |
Hydraulic circuit | ||
Evaporator volume | dm3 | 3.63 |
Loss of coolant pressure in the heat exchanger | kPa | 28 |
Coolant flow | m3/h | 1.7 |
OVERALL DIMENSIONS | ||
Width | mm | 685 |
Depth | mm | 485 |
Height | mm | 1100 |
Weight | kg | 140 |
CONNECTING DIMENSIONS | ||
Connection diameter of coolant pipelines inlet/outlet | inch | 1 1/4 |
Condensate drain diameter | mm | 20 |