RU | EN Mon-Fri 09:00 - 18:00
Air conditioners are designed to continuously maintain the temperature, humidity and volume and purity of air flow .
ROW unit is a multi-split system, designed for high density CED system
HIGH TECHNOLOGY EQUIPMENT VYBOS
DEVELOPMENT AND MANUFACTURE

NON-AUTONOMOUS AIR CONDITIONERS VYBOS ВСУ008ХБ

VYBOS ВСУ008ХБ is a high-precision and durable air conditioner designed for cooling critical infrastructure and engineering systems.
Overall dimensions allow the ВСУ008ХБ to be placed in small compact rooms.
The presence of easily removable modules greatly simplifies service and maintenance.

Main components

 

Execution

Grilles with adjustable flow direction
Silencers
Electronically commutated fan
Heat exchanger
Load base
Screws for quick removal of panels
 



 

Technical characteristics ВСУ008ХБ

Indoor unit model    ВСУ008ХБ
External block model   -
Number of external blocks   -
INITIAL PARAMETERS
Coolant type   Water
Coolant inlet temperature °С 7
Outlet coolant temperature °С 12
Air temperature at the air conditioner inlet °С 24
Relative humidity at the air conditioner inlet % 50
Ambient temperature °С -
Altitude m -
EQUIPMENT PARAMETERS
Power supply   220V/1ph/50Hz+N+PE
Total cooling capacity kW 10
Sensible cooling capacity kW 8.5
SHR   0.85
Air temperature at the outlet of the air conditioner °С 11.4
Air humidity at the outlet of the air conditioner % 90
FAN SECTION
Air flow m3/h 1800
Rated power consumption kW 0.27
Maximum operating current A 2,1
Maximum external static pressure    
Number of fans pcs 1
AIR FILTERS
Filter class   G4
SOUND PRESSURE
Sound pressure level dB 35
Hydraulic circuit    
Evaporator volume dm3 3.63
Loss of coolant pressure in the heat exchanger kPa 28
Coolant flow m3/h 1.7
OVERALL DIMENSIONS
Width mm 685
Depth mm 485
Height mm 1100
Weight kg 140
CONNECTING DIMENSIONS
Connection diameter of coolant pipelines inlet/outlet inch 1 1/4
Condensate drain diameter mm 20