Air conditioners are designed to continuously maintain the temperature, humidity and volume and purity of air flow .
ROW unit is a multi-split system, designed for high density CED system
HIGH TECHNOLOGY EQUIPMENT VYBOS
DEVELOPMENT AND MANUFACTURE

AUTONOMOUS AIR CONDITIONERS VYBOS ВСУ050BC

VYBOS ВСУ050BC is a high-precision and durable air conditioner, resistant to the effects of seismic shock overload (half-wave amplitude of the acceleration pulse 20g (196 m/s) and duration 30-50ms).
VYBOS ВСУ050BC have the accuracy of maintaining the air temperature in the room: ± 1°C. Accuracy of maintaining indoor air humidity: ± 5%.
ВСУ050BC operates effectively in any climatic zones.

 

ВСУ050BC version with fan section
 
ВСУ050BC version without fan section
Air conditioners with a fan section Air conditioners with a fan section   Air conditioners without a fan section Air conditioners without a fan section

 

Main components

LCD display with Russian-language menu
Air valve
Electronically commutated fan
Electrical cabinet
Water supply
Water condenser
Double compressor protection system against high/low pressure
Filter drier
Compressor
Differential relays for monitoring fan operation
Freon circuit with water cooling of the condenser
Freons R22, R410A, R407C
Cooling water range: from +5°C to +21°C.

 

Technical characteristics ВСУ050BC

MAIN CHARACTERISTICS
Indoor unit model   ВСУ050BC
Water condenser   D62L-70
Number of contours   1
INITIAL PARAMETERS
Refrigerant type   R22
Air temperature at the air conditioner inlet °С 27
Relative humidity at the air conditioner inlet % 60
Altitude m 0
EQUIPMENT PARAMETERS
Power supply   400/3ph/50Hz+N+PE
Total cooling capacity kW 48.9
Sensible cooling capacity kW 46.6
SHR   0.95
EER    
Outgoing air temperature °С 12.5
Outgoing air humidity °С 91.1
FAN SECTION
Air flow m 3/h 9000
Rated power consumption kW 2.9
Maximum operating current A 4,4
Maximum external static pressure Pa 526
Number of fans pcs 1
COMPRESSOR
Number of compressors / circuits   1
Compressor type   Spiral
Rated power consumption kW 11
Maximum operating current A 35
Current with locked rotor A 175
CAN-COOLED CONDENSER
Water consumption m 3/h 8.6
Coolant % Water
Temperature graph of coolant °С 21/24
Pressure drop kPa 37.6
EVAPORATOR
Evaporator volume dm 3 14.7
SOUND PRESSURE
Sound pressure level dB 61
OVERALL DIMENSIONS
Width mm 1200
Depth mm 790
Height mm 1951
Weight kg 510
CONNECTING DIMENSIONS
Condenser input/output connection diameter inch 1 1/4
Condensate drain diameter mm 20