Main components
LCD display with Russian-language menu
Air valve
Electronically commutated fan
Electrical cabinet
Water supply
Water condenser
Double compressor protection system against high/low pressure
Air valve
Electronically commutated fan
Electrical cabinet
Water supply
Water condenser
Double compressor protection system against high/low pressure
Filter drier
Compressor
Differential relays for monitoring fan operation
Freon circuit with water cooling of the condenser
Freons R22, R410A, R407C
Cooling water range: from +5°C to +21°C.
Compressor
Differential relays for monitoring fan operation
Freon circuit with water cooling of the condenser
Freons R22, R410A, R407C
Cooling water range: from +5°C to +21°C.
Technical characteristics ВСУ050BC
MAIN CHARACTERISTICS | ||
Indoor unit model | ВСУ050BC | |
Water condenser | D62L-70 | |
Number of contours | 1 | |
INITIAL PARAMETERS | ||
Refrigerant type | R22 | |
Air temperature at the air conditioner inlet | °С | 27 |
Relative humidity at the air conditioner inlet | % | 60 |
Altitude | m | 0 |
EQUIPMENT PARAMETERS | ||
Power supply | 400/3ph/50Hz+N+PE | |
Total cooling capacity | kW | 48.9 |
Sensible cooling capacity | kW | 46.6 |
SHR | 0.95 | |
EER | ||
Outgoing air temperature | °С | 12.5 |
Outgoing air humidity | °С | 91.1 |
FAN SECTION | ||
Air flow | m 3/h | 9000 |
Rated power consumption | kW | 2.9 |
Maximum operating current | A | 4,4 |
Maximum external static pressure | Pa | 526 |
Number of fans | pcs | 1 |
COMPRESSOR | ||
Number of compressors / circuits | 1 | |
Compressor type | Spiral | |
Rated power consumption | kW | 11 |
Maximum operating current | A | 35 |
Current with locked rotor | A | 175 |
CAN-COOLED CONDENSER | ||
Water consumption | m 3/h | 8.6 |
Coolant | % | Water |
Temperature graph of coolant | °С | 21/24 |
Pressure drop | kPa | 37.6 |
EVAPORATOR | ||
Evaporator volume | dm 3 | 14.7 |
SOUND PRESSURE | ||
Sound pressure level | dB | 61 |
OVERALL DIMENSIONS | ||
Width | mm | 1200 |
Depth | mm | 790 |
Height | mm | 1951 |
Weight | kg | 510 |
CONNECTING DIMENSIONS | ||
Condenser input/output connection diameter | inch | 1 1/4 |
Condensate drain diameter | mm | 20 |