Air conditioners are designed to continuously maintain the temperature, humidity and volume and purity of air flow .
The precision inter-row air conditioner "VYBOS VR6050FTE1SIV0" is designed to provide the required temperature and humidity conditions in technological rooms: server rooms, data processing centers, computer rooms, etc.
All models are supplied with built-in fans, compressors, additional components (steam humidifier, heater), control controller with user interface and internal wiring. The body, frame and cladding are made of galvanized steel.
ВР6050ФТЭ1СИВ0 | ||
TECHNICAL DATA | ||
Total cooling capacity | kW | 51.6 |
Perceptible cooling capacity | kW | 48.4 |
Heat transfer efficiency coefficient, SHR | 0.94 | |
Sound pressure level at a height of 1.5 m and a distance of 2 m from the front panel of the air conditioner, with the compressor and fan running | dBA | 72 |
Freon | R410a | |
Number of refrigerant circuits | 1 | |
Evaporator volume | dm3 | 11.1 |
ENERGY CONSUMPTION | ||
Compressor | kW | 13.1 |
Fan | kW | 1.7 |
Humidifier | kW | 1,1 |
Heater | kW | 0 |
Capacitor | kW | 1,4 |
COMPRESSOR | ||
Type | Inverter | |
ELECTRICAL CHARACTERISTICS | ||
Power supply | 400 V / 3 ph / 50 Hz | |
Compressor | A | 26.6 |
Fan | A | 3.6 |
Humidifier | A | 8.2 |
Heater | A | 0 |
Capacitor | A | 6 |
OVERALL DIMENSIONS | ||
Length | mm | 1200 |
Width | mm | 600 |
Height | mm | 2000 |
Weight | mm | 335 |
PERFORMANCE LIMITS | ||
Indoor air parameters | °С | from 18, 30% R.H. up to 45, 80% R.H. |
Storage conditions | °С | from – 20° up to 50° |
Tolerable supply voltage deviations | V +- 10%, Hz +- 2 |