RU | EN Mon-Fri 09:00 - 18:00
Air conditioners are designed to continuously maintain the temperature, humidity and volume and purity of air flow .
ROW unit is a multi-split system, designed for high density CED system
HIGH TECHNOLOGY EQUIPMENT VYBOS
DEVELOPMENT AND MANUFACTURE

PRECISION AIR CONDITIONERS WITH REMOTE AIR CONDENSER

The heat from the technical room is dissipated by an external finned coil condenser, connected during installation. Remote condensers are available in standard and silenced version.

BLOCK IDENTIFICATION

1 2 3 4,5,6 7 8 9 10 11 12 13 14

В Р 6 050 Ф Т Э 1 С И Н 00

 

1. MANUFACTURER
B - VYBOS

2. SERIES
Р - inter-row

3. SIZE: WIDTH
3=300 mm
5=500 mm
6=600 mm

4,5,6. NOMINAL
COOLING CAPACITY:
Nominal
cooling capacity,
kW
7. TYPE:
Ф = Precision air conditioners with a remote air-cooled condenser
B = Precision air conditioners with a built-in water-cooled condenser
X = Precision air conditioners using cold
(chiller) water

8. AIR DIRECTION (DISCHARGE)
T = rear suction, forward discharge
Д = closed circuit, side suction/discharge
Л = closed circuit, left suction/discharge
П = closed kennel, suction/discharge on the right
9. TYPE OF FAN
Э = Electronically commutated
A = Asynchronous

10. TYPE OF REFRIGERANT
0 = water
1 = R410A
2 = R407C
3 = R134A

11. MODIFICATION
C = Standard (compressor located inside)
K = Compressor located outside< /td>12. COMPRESSOR TYPE
0 = without compressor
1 = compressor with “on off”
И = compressor with inverter (frequency) control

13. COOLANT SUPPLY SIDE
B = top
H = bottom

14. CONSTRUCTION:
00 = Standard
XX = Non-standard

 

VR3 precision air conditioners

ВР3 Ф SERIES
Model range: ВР3015Ф | ВР3020Ф | ВР3025Ф

  • Refrigerant: Freon
  • Total cooling capacity:16.18-25.6 kW
  • Power supply: 380V / 3F / 50Hz+N+PE
  • Air flow: 2200-4000 m3/h
  • Dimensions (width x depth x height): 300x1000x2000 mm
  • Weight:185-190kg

Find out price

 

ВР3 Ф - a market-leading data center and electronics cooling solution, an innovative and efficient thermal management system for rooms, rows and racks, from small computer rooms to large mission-critical data centers .

 

Full control of the cooling
of your room
Possibility of developing
a constructive solution
for a specific project
Compatible with communication protocols (Modbus, SNMP, Lonworks, Bacnet, etc.), BMS building management systems and engineering systems Equipped with a wide range of
additional options

 

BP3 Ф BASIC OPTIONS

Basic options for in-row air conditioners of the BP3 Ф series. List of basic equipment used with cPCO controllers.
See table for ВР3 Ф

 

DETAILED TECHNICAL CHARACTERISTICS OF ВР3 Ф SERIES

    ВР 3 015 F BP 3 020 F BP 3 025 F
Indoor unit model   ВК 019 СТД Н ВК 028 СТД Н ВК 033 СТД Н
Number of external blocks   1 1 1
EQUIPMENT PARAMETERS
Power supply   380/3ph/50Hz+N+PE
Total cooling capacity kW 16,18 20.56 25.6
Sensible cooling capacity kW 15.50 20.38 24.7
SHR   0.96 0.99 0.96
FAN SECTION
Air flow m3/h 2200 3200 4000
Maximum power consumption kW 0.16 0.16 0.16
Maximum operating current A 1.26 1.26 1.26
Maximum external static pressure Pa 250 250 250
Number of fans pcs 4 5 5
COMPRESSOR
Number of compressors / circuits   1 1 1
Compressor type   Spiral Spiral Spiral
Rated power consumption kW 4.33 5.18 6.5
Rated operating current A     9.5
Maximum operating current A 8,8 10.89 15.5
HUMIDIFICATION
Steam capacity kg/h 3 3 3
Rated power consumption kW 2,2 2,2 2,2
Maximum operating current A 10.2 10.2 10.2
ELECTRIC HEATER
Number of steps   1 1 1
Rated power consumption/heating power kW 4.26 4.26 4.26
Maximum operating current A 6,7 6,7 6,7
AIR FILTERS
Filter class   G4 G4 G4
EVAPORATOR
Evaporator volume dm3 6.13 6.13 6.13
SOUND PRESSURE
Sound pressure level ³ dB 63 71 76
OVERALL DIMENSIONS
Width mm 300 300 300
Depth mm 1000|1200 1000|1200 1000|1200
Height mm 1998 1998 1998
Weight ² kg 190 185 190
CONNECTING DIMENSIONS
Gas pipe diameter mm 16 16 16
Diameter of liquid pipe mm 12 12 16
Water supply diameter for humidifier Inch ¾ ¾ 3/4
Diameter of water drainage from the humidifier mm 32 32 32
Condensate drain diameter mm 20 20 20

 

 

VR6 precision air conditioners

ВР6 Ф SERIES
Model range: ВР6035Ф | ВР6050Ф

  • Refrigerant: Freon
  • Total cooling capacity:37.3-51.6 kW
  • Power supply: 380V / 3F / 50Hz+N+PE
  • Air flow: 6000-6850 m3/h
  • Dimensions (width x depth x height): 600x1200x2000 mm
  • Weight: 280-335kg

Find out price

 

ВР6 Ф - a line of in-row air conditioners, provides an effective, flexible, economical and reliable approach to creating comfortable conditions in data centers, telecommunications centers and server rooms. Take complete control of your data center cooling.

 

Full control of the cooling
of your room
Possibility of developing
a constructive solution
for a specific project
Compatible with communication protocols (Modbus, SNMP, Lonworks, Bacnet, etc.), BMS building management systems and engineering systems Equipped with a wide range of
additional options

 

BP6 Ф BASIC OPTIONS

Basic options for in-row air conditioners of the ВР6 Ф series. List of basic equipment used with cPCO controllers.
See table for VR6 F

 

DETAILED TECHNICAL CHARACTERISTICS ВР6 Ф SERIES

    BP 6 035 Ф BP 6 050 Ф
Indoor unit model   ВК 050 СТД Н ВК 064 СТД Н
Number of external blocks   1 1
EQUIPMENT PARAMETERS
Power supply   380/3ph/50Hz+N+PE
Total cooling capacity kW 37.3 51.6
Sensible cooling capacity kW 37.3 48.4
SHR   1 0.94
FAN SECTION
Air flow m3/h 6000 6850
Maximum power consumption kW 1,1 1,1
Maximum operating current A 1.76 1.76
Maximum external static pressure Pa 381 250
Number of fans pcs 2 2
COMPRESSOR
Number of compressors / circuits   1 1
Compressor type   Spiral Spiral
Rated power consumption kW 11.6 13.06
Rated operating current A    
Maximum operating current A 19.8 26.64
HUMIDIFICATION
Steam capacity kg/h 3 3
Rated power consumption kW 1.07 1.07
Maximum operating current A 8.2 8.2
ELECTRIC HEATER
Number of steps   1 1
Rated power consumption/heating power kW 4.32 4.32
Maximum operating current A 6,7 6,7
AIR FILTERS
Filter class   G4 G4
EVAPORATOR
Evaporator volume dm3 8.2 11.07
SOUND PRESSURE
Sound pressure level ³ 76 87 87
OVERALL DIMENSIONS
Width mm 600 600
Depth mm 1000|1200 1200
Height mm 1998 1998
Weight ² kg 280 335
CONNECTING DIMENSIONS
Gas pipe diameter mm 18 28
Diameter of liquid pipe mm 16 22
Water supply diameter for humidifier Inch 3/4 ¾
Diameter of water drainage from the humidifier mm 32 32
Condensate drain diameter mm 20 20

¹ – dry bulb
² – weight of basic equipment
³ – sound pressure level for free space conditions at a distance of 1 meter