BLOCK IDENTIFICATION

1 2 3 4,5,6 7 8 9 10 11 12 13 14

В Ш Б 058 Х Н Э 1 С И 0 X

 

1. MANUFACTURER
В - VYBOS

2. SERIES
Ш - cabinet

3. COOLING CAPACITY RANGE:
M = SMALL
C = MEDIUM
Б = LARGE
Э = EXTRA

4,5,6. NOMINAL
COOLING CAPACITY:
Nominal
cooling capacity,
kW
7. TYPE:
Ф = Precision air conditioners with a remote air-cooled condenser
B = Precision air conditioners with a built-in water-cooled condenser
X = Precision air conditioners using cold (chiller) water

8. DIRECTION AIR (DISCHARGE):
H = Suction vertically from above, discharge vertically downwards
B = Suction vertically from below, delivery vertically upwards
B = Suction from below, delivery vertically upwards
Ф = Suction top, front feed bottom front
9. TYPE OF FAN
E = Electronically commutated
A = Asynchronous

10. TYPE OF REFRIGERANT
0 = water
1 = R410A
2 = R407C
3 = R134A

11. MODIFICATION
C = Standard (compressor located inside)
K = Compressor located outside< /td>12. COMPRESSOR TYPE
0 = without compressor
1 = compressor with “on-off” control
И = compressor with inverter (frequency) control

13. COOLANT SUPPLY SIDE
0 = choice not available

14. CONSTRUCTION:
0 = Standard
X = Custom

 

 

шкафные кондиционеры ВШМ

ВШМ Х SERIES
Model range: ВШМ008ХН | ВШМ010ХН | ВШМ012ХН | ВШМ015ХН | ВШМ020ХН | ВШМ027ХН

  • Refrigerant:Water
  • Total cooling capacity:8.52-22.14 kW
  • Air flow:1700-5400 m3/h
  • Dimensions (width x depth x height):670x500x1750 mm, 770x650x1980mm
  • Weight: 95kg, 160kg

Find out price

 

ВШМ X is a family of compact chilled water precision air conditioning systems for mission critical environments where reliability, availability and energy efficiency are key to the continued and successful operation of all systems.

 

Full control of the cooling
of your room
Possibility of developing
a constructive solution
for a specific project
Compatible with communication protocols (Modbus, SNMP, Lonworks, Bacnet, etc.), BMS building management systems and engineering systems Equipped with a wide range of
additional options

 

BASIC OPTIONS OF ВШМ X

Basic options for cabinet air conditioners of the ВШМ X series. List of basic equipment used with cPCO controllers.
See table for ВШМ X

 

TECHNICAL DATA ВШМ Х

    ВШМ 008 ХН ВШМ 010 ХН ВШМ 012 ХН ВШМ 015 ХН ВШМ 020 ХН ВШМ 027 ХН
INITIAL PARAMETERS
Refrigerant type   Water
Coolant inlet temperature ° C 7 7 7 7 7 7
Outlet coolant temperature % 12 12 12 12 12 12
Air temperature at the air conditioner inlet ¹ ° C 24 24 24 24 24 24
Relative air humidity at the air conditioner inlet % 50 50 50 50 50 50
EQUIPMENT PARAMETERS
Power supply   380/3ph/50Hz+N+PE
Total cooling capacity kW 8.52 12.65 13.9 19.6 21.07 22.14
Sensible cooling capacity kW 7.19 10.45 11.51 16.1 17.36 18.32
SHR   0.83 0.83 0.83 0.82 0.82 0.83
Air temperature at the outlet of the air conditioner ° C 11.7 11.9 12.1 13.6 13.9 14.2
Air humidity at the outlet of the air conditioner % 97.5 95.2 94.4 86.2 85 84.1
FAN SECTION
Air flow m3/h 1700 2500 2800 4500 5000 5400
Maximum power consumption kW 1,1 1,1 1,1 1,1 4.2 4.2
Maximum operating current A 1.76 1.76 1.76 1.76 9.3 9.3
Maximum external static pressure Pa 250 250 250 600 600 600
Number of fans pcs 1 1 1 1 1 1
HUMIDIFICATION
Steam capacity kg/h 1.5-3 1.5-3 1.5-3 5-8 5-8 5-8
Rated power consumption kW 1.13- 2.25 1.13- 2.25 1.13- 2.25 3.64- 6.06 3.64- 6.06 3.64- 6.06
Maximum operating current A 4.9-9.8 4.9-9.8 4.9-9.8 9.4 9.4 9.4
ELECTRIC HEATER
Number of steps   1 1 1 1 1 1
Rated power consumption/heating power kW 1.42 1.42 1.42 1.42 4.32 4.32
Maximum operating current A 6.59 6.59 6.59 6.59 6,7 6,7
AIR FILTERS
Filter class   G4 G4 G4 G4 G4 G4
SOUND PRESSURE
Sound pressure level ³ dB 63 64 50 69 69 69
HYDRAULIC CIRCUIT
Evaporator volume dm3 6.73 6.73 6.73 7.05 7.05 7.05
Loss of coolant pressure in the heat exchanger kPa 7.4 15.9 19.1 24 27.3 29.9
Coolant flow m3/h 1.5 2,2 2,4 3,4 3.6 3.8
OVERALL DIMENSIONS
Width mm 670 670 670 770 770 770
Depth mm 500 500 500 650 650 650
Height mm 1750 1750 1750 1980 1980 1980
Weight ² kg 95 95 95 160 160 160
CONNECTING DIMENSIONS
Connection diameter of coolant pipelines inlet/outlet   ¾ HP ¾ HP ¾ HP 1 1/4 HP 1 1/4 HP 1 1/4 HP
Water supply diameter for humidifier Inch ¾ VR ¾ VR ¾ VR ¾ VR ¾ VR ¾ VR
Diameter of water drainage from the humidifier mm 32 32 32 32 32 32
Condensate drain diameter mm 20 20 20 20 20 20

 

 

шкафные кондиционеры ВШC

ВШС Х SERIES
Model range: ВШС030ХН | ВШС040ХН | ВШС045ХН |ВШС055ХН

  • Refrigerant:Water
  • Total cooling capacity:39.7-63.2 kW
  • Air flow:6700-13000 m3/h
  • Dimensions (width x depth x height):960x890x1980 mm, 1460x890x1980mm
  • Weight: 295kg, 380kg

Find out price

 

ВШС X - a complete line of high-quality, high-performance systems will help you solve even complex problems in the design and construction of air conditioning in your premises.
Just like other lines, it is equipped with electronically commutated EC fans, which increase cooling capacity, reduce energy consumption, and reduce noise characteristics.

 

Full control of the cooling
of your room
Possibility of developing
a constructive solution
for a specific project
Compatible with communication protocols (Modbus, SNMP, Lonworks, Bacnet, etc.), BMS building management systems and engineering systems Equipped with a wide range of
additional options

 

BASIC OPTIONS OF ВШС X

Basic options for cabinet air conditioners of the ВШС X series. List of basic equipment used with cPCO controllers.
See table for ВШС X

 

TECHNICAL DATA ВШС X

    ВШС 030 ХН ВШС 040 ХН ВШС 045 ХН ВШС 055 ХН
INITIAL PARAMETERS
Refrigerant type   Water
Coolant inlet temperature ° C 7 7 7 7
Outlet coolant temperature % 12 12 12 12
Air temperature at the air conditioner inlet ¹ ° C 24 24 24 24
Relative air humidity at the air conditioner inlet % 50 50 50 50
EQUIPMENT PARAMETERS
Power supply   380/3ph/50Hz+N+PE
Total cooling capacity kW 39.7 46.7 56.1 63.2
Sensible cooling capacity kW 31 36.8 45.2 51.4
SHR   0.78 0.78 0.81 0.81
Air temperature at the outlet of the air conditioner ° C 10.6 11 12.1 12.5
Air humidity at the outlet of the air conditioner % 97.4 96.4 92.5 91
FAN SECTION
Air flow m3/h 6700 8200 11000 13000
Maximum power consumption kW 4.2 4.2 4.2 4.2
Maximum operating current A 9.3 9.3 9.3 9.3
Maximum external static pressure Pa 600 295 525 418
Number of fans pcs 1 1 2 2
HUMIDIFICATION
Steam capacity kg/h 5-8 5-8 5-8 5-8
Rated power consumption kW 3.64- 6.06 3.64- 6.06 3.64- 6.06 3.64- 6.06
Maximum operating current A 9.4 9.4 9.4 9.4
ELECTRIC HEATER
Number of steps   1 1 2 2
Rated power consumption/heating power kW 4.32 4.32 8.64 8.64
Maximum operating current A 6,7 6,7 13.4 13.4
AIR FILTERS
Filter class   G4 G4 G4 G4
SOUND PRESSURE
Sound pressure level ³ dB 71 71 72 72
HYDRAULIC CIRCUIT
Evaporator volume dm3 20.48 20.48 22.1 22.1
Loss of coolant pressure in the heat exchanger kPa 17.8 20.4 33.9 42.8
Coolant flow m3/h 6.8 8 9.6 10.8
OVERALL DIMENSIONS
Width mm 960 960 1460 1460
Depth mm 890 890 890 890
Height mm 1980 1980 1980 1980
Weight ² kg 295 295 380 380
CONNECTING DIMENSIONS
Connection diameter of coolant pipelines inlet/outlet   1 1/2 HP 1 1/2 HP 1 1/2 HP 1
Water supply diameter for humidifier Inch ¾ VR ¾ VR ¾ VR ¾ VR
Diameter of water drainage from the humidifier mm 32 32 32 32
Condensate drain diameter mm 20 20 20 20

 

 

шкафные кондиционеры ВШБ

ВШБ Х SERIES
Model range: ВШБ060ХН | ВШБ080ХН | ВШБ090ХН | ВШБ110ХН

  • Refrigerant:Water
  • Total cooling capacity:78.02-118.6 kW
  • Air flow:15500- 22500 m3/h
  • Dimensions (width x depth x height):(1680,2120) x 890 x 1980mm
  • Weight: 380-690kg

Find out price

 

ВШБ Х - a range of cabinet air conditioners that meet your air handling and conditioning requirements, efficiency and energy consumption standards, reliability requirements and high cooling capacity.

 

Full control of the cooling
of your room
Possibility of developing
a constructive solution
for a specific project
Compatible with communication protocols (Modbus, SNMP, Lonworks, Bacnet, etc.), BMS building management systems and engineering systems Equipped with a wide range of
additional options

 

BASIC OPTIONS OF ВШБ X

Basic options for cabinet air conditioners of the VShB X series. List of basic equipment used with cPCO controllers.
See table for ВШБ X

 

TECHNICAL DATA ВШБ X

    ВШБ
060 ХН
ВШБ
080 ХН
ВШБ
090 ХН
ВШБ
110 ХН
Refrigerant type   Water
Coolant inlet temperature ° C 7 7 7 7
Outlet coolant temperature % 12 12 12 12
Air temperature at the air conditioner inlet ¹ ° C 24 24 24 24
Relative air humidity at the air conditioner inlet % 50 50 50 50
EQUIPMENT PARAMETERS
Power supply   380/3ph/50Hz+N+PE
Total cooling capacity kW 78.02 83.2 104.3 118.6
Sensible cooling capacity kW 62.34 67.8 84.3 92.8
SHR   0.81 0.82 0.81 0.78
Air temperature at the outlet of the air conditioner ° C 2.5 12.6 12.1 12
Air humidity at the outlet of the air conditioner % 91 90 80 90.7
FAN SECTION
Air flow m3/h 15500 17000 20000 22500
Maximum power consumption kW 4.2 4.2 4.2 4.2
Maximum operating current A 9.3 9.3 9.3 9.3
Maximum external static pressure Pa 456 359 350 250
Number of fans pcs 2 2 2 2
HUMIDIFICATION
Steam capacity kg/h 5-8 5-8 5-8 5-8
Rated power consumption kW 3.64- 6.06 3.64- 6.06 3.64- 6.06 3.64- 6.06
Maximum operating current A 9.4 9.4 9.4 9.4
ELECTRIC HEATER
Number of steps   2 2 3 2
Rated power consumption/heating power kW 8.64 8.64 12.78 8.64
Maximum operating current A 13.4 13.4 19.47 13.4
AIR FILTERS
Filter class   G4 G4 G4 G4
SOUND PRESSURE
Sound pressure level ³ dB 72 74 76 76
HYDRAULIC CIRCUIT
Evaporator volume dm3 22.1 27.5 39.11 45.04
Loss of coolant pressure in the heat exchanger kPa 42.8 38.8 39 40.9
Coolant flow m3/h 10.8 14.3 18 20.3
OVERALL DIMENSIONS
Width mm 1680 1680 2120 2120
Depth mm 890 890 890 890
Height mm 1980 1980 1980 1980
Weight ² kg 380 480 380 690
CONNECTING DIMENSIONS
Connection diameter of coolant pipelines inlet/outlet   1/2 HP 2 HP 2 HP Coupling
Victaulic
Ø76
(3 inches).
Water supply diameter for humidifier Inch ¾ VR ¾ VR ¾ VR ¾ VR
Diameter of water drainage from the humidifier mm 32 32 32 32
Condensate drain diameter mm 20 20 20 20

 

 

шкафные кондиционеры ВШЭ

ВШЭ Х SERIES
Model range: ВШЭ125ХН | ВШЭ150ХН | ВШЭ170ХН | ВШЭ200ХН

  • Refrigerant:Water
  • Total cooling capacity:138.4-201.2 kW
  • Air flow:22000-40000 m3/h
  • Dimensions (width x depth x height):(2580,3600) x 890 x 1980mm
  • Weight: 800,1035kg

Find out price

 

ВШЭ X - a line of cabinet air conditioners provide an effective, economical, reliable and flexible approach to creating a comfortable atmosphere in rooms with large spaces.

 

Full control of the cooling
of your room
Possibility of developing
a constructive solution
for a specific project
Compatible with communication protocols (Modbus, SNMP, Lonworks, Bacnet, etc.), BMS building management systems and engineering systems Equipped with a wide range of
additional options

 

TECHNICAL DATA ВШЭ X

    ВШЭ
125 ХН
ВШЭ
150 ХН
ВШЭ
170 ХН
ВШЭ
200 ХН
Refrigerant type   Water
Coolant inlet temperature ° C 7 7 7 7
Outlet coolant temperature % 12 12 12 12
Air temperature at the air conditioner inlet ¹ ° C 24 24 24 24
Relative air humidity at the air conditioner inlet % 50 50 50 50
EQUIPMENT PARAMETERS
Power supply   380/3ph/50Hz+N+PE
Total cooling capacity kW 138.4 162.2 179.4 201.2
Sensible cooling capacity kW 104.8 124.2 141.7 160.4
SHR   0.75 0.77 0.79 0.8
Air temperature at the outlet of the air conditioner ° C 10.6 11.2 11.9 12.4
Air humidity at the outlet of the air conditioner % 91 90 91.9 90.4
FAN SECTION
Air flow m3/h 22000 27000 34000 40000
Maximum power consumption kW 4.2 4.2 4.2 3
Maximum operating current A 9.3 9.3 9.3 6.5
Maximum external static pressure Pa 289 289 300 250
Number of fans pcs 3 3 4 4
HUMIDIFICATION
Steam capacity kg/h 5-8 5-8 5-8 5-8
Rated power consumption kW 3.64- 6.06 3.64- 6.06 3.64- 6.06 3.64- 6.06
Maximum operating current A 9.4 9.4 9.4 9.4
ELECTRIC HEATER
Number of steps   3 3 3 3
Rated power consumption/heating power kW 13 13 12.96 12.96
Maximum operating current A 20.1 20.1 20.1 20.1
AIR FILTERS
Filter class   G4 G4 G4 G4
SOUND PRESSURE
Sound pressure level ³ dB 76 77 78 78
HYDRAULIC CIRCUIT
Evaporator volume dm3 27.5 27.5 81.96 81.96
Loss of coolant pressure in the heat exchanger kPa 60.6 81.8 42.6 52.8
Coolant flow m3/h 23.8 27.8 30.8 34.6
OVERALL DIMENSIONS
Width mm 2580 2580 3600 3600
Depth mm 890 890 890 890
Height mm 1980 1980 1980 1980
Weight ² kg 800 800 1035 1035

¹ – dry bulb
²– weight of basic equipment
³ – sound pressure level for free space conditions at a distance